Oxygen Deficiency Alarm for Low Temperature
Our RAD-0002-ZR Oxygen Deficiency Alarm for Low Temperature, protects staff in enclosed areas near storage cylinders of nitrogen, argon, ammonia, chlorine, propane, nitrous oxide, helium, argon, or other inert gases.
Per both the Occupational Safety and Health Administration (OSHA) and National Institutes of Health (NIH) hazardous conditions may include areas where the oxygen concentrations fall below 19.5% or above 23.5% and require oxygen deficiency monitors.
Our Oxygen Deficiency Alarm for Low Temperatures is commonly used in hospitals, laboratories, pharmaceuticals, cryogenics, process cooling, freezers, manufacturing, food + beverage, and research facilities.
The oxygen deficiency safety monitor will stay accurate at temperatures as low as -50°C, without needing maintenance and does not require zero calibration.
Advantages
- Operates at severe low temperatures and freezers at -50ºC
- Real-time oxygen level readout on sensor and remote display
- Audible and flashing alarm on the sensor and remote display (90db)
- 3 user-configurable alarms meet all OSHA codes
- The remote display can be mounted up to 300 feet away
- Easy to install, no maintenance required
- CE Listed
- International Power Supply (included)
- 10+ years of sensor life expectancy
Add-On Options
RAD-0022: Add-on Remote Display for RAD-0002 Oxygen Depletion Safety Alarm above. Order up to 2 additional add-on displays to cover 3 entrances. Uses industry-standard RJ45 Ethernet cable (not included) to install up to 300 feet away.
CM-1027: Dual Strobe Add On Kit. Plug flashing strobes into both the sensor and remote display to give a more visual alarm. Used in high-noise environments or where required by an inspector.
CM-1026-5: 100-240 VAC Strobe Tower Add-On Kit - yellow, orange, and red indicate alarm levels 1-3. Adds visual notice and high decibel alarm.
CM-1026-6: 24 VDC Strobe Tower Add-On Kit - same features as CM-1026-5 for 24 VDC hard-wired systems.
Certificate of Calibration - Available on request in comments at purchase. For factory recalibration order part no. CAL-0001 here
Specifications
- Measurement Range: 0-25% display
- Sensor Life Expectancy: 10 years
- Alarms O2 AL1: 18.0%, 18.5%, 19.0%, 19.5%, 20.0%. The default AL1 is 19.0%.
- Alarms O2 AL2: 16.0%, 16.5%, 17.0%, 17.5%. The default AL2 is 17.0%
- Alarm Response Time: < 60 seconds
- Operating Temperature: -58°F to 122°F (-50°C to 50°C)
Electrical
- Power Supply: Output: 12VDC, 2000mA.
- Power Input: 100~240 VAC, 50/60Hz, 0.6A
- 25 ft. Ethernet cable (included)
- Power Consumption: 3 Watts
- 6 VDC battery backup connections
- Relays: Peak Current < 2A @ 30 VDC or 250 VAC, SPDT
- 4-20mA output
Warranty
- 1 year on the device, 2 years on the sensor. See CO2Meter Terms + Conditions
RAD-0022 Add-on Remote Display for RAD-0002 Oxygen Depletion Safety Alarm above. Order up to 2 additional add-on displays to cover 3 entrances. Uses industry-standard RJ45 Ethernet cable (not included) to install up to 300 feet away.
CM-1027: Dual Strobe Add On Kit. Attach a flashing strobe to both the sensor and remote display to give a more visual alarm. Used in high-noise environments or where required by an inspector.
CM-1026-5: 100-240 VAC Strobe Tower Add-On Kit - yellow, orange, and red indicate alarm levels 1-3. Adds visual notice and high decibel alarm.