CO2 Multi Sensor System
The CO2 Multi-Sensor System is designed to detect Carbon Dioxide (CO2) levels in the ambient air to protect employees, workers, and establishments.
CO2 monitors are required in most jurisdictions by code and regulation.
The CM-7000 features both audible and visual alarms as well as the ability to configure sensors independently including the 3 relays that are triggered at 5,000 TWA, 5000 ppm, 1.5% CO2, and 3% to meet OSHA/NIOSH standards including local fire codes.
Users may configure modules (sensor, horn/strobe, and key switch) from any tablet either in direct connection or through daisy-chaining modules together. You may not exceed 12 horn/strobe modules on any string.
With the CM-7000, you can ensure that you and your employees are safe and protected, and should an incident occur rely on the CM-7000's ability to trigger an exhaust fan or send an immediate alarm to the fire department or monitoring company.
Please note: *High concentrations of carbon dioxide in confined spaces are dangerous and may lead to negative health problems ranging from fatigue, asphyxiation, or even fatality, if not properly monitored.*
Features
- 8" Touch Screen Display Panel
- 12 easily addressable CO2 Sensors
- 100% Clean, Modern Appearance - All cables can be hidden
- Customer Configurable Alarm and Notification Settings
- Mute Push Button to temporarily mute audible alarms
- Integrated Speaker and USB port
- Meets NFPA, IFC, and NBIC Requirements
- Meets OSHA and NIOSH TWA Standards
- Meets all local municipality inspection codes and requirements
Models
CM-7000 - CO2 Multi-Sensor System - Includes: (1 Main 8" Touchscreen Control Tablet, 2 Sensor Units, 2 Horn Strobes, Mounting Hardware, Cables, Power Supply and Safety Signage.)
CM-7001 - Sensor Unit and Horn Strobe Add On
CM-7002 - Reset Unit Add On
CM-7003- Sensor Unit Add On
CM-7004- Horn Strobe Add On
SV-1027 - CM-7000 Solenoid Valve Shut Off Add On
Applications
- Restaurant and Food
- Breweries and Wineries
- Beverage Dispensing
- Medical and Scientific
- Agriculture
- Safety
Specifications
- Measurement Range: 0-5% (0-50,000 ppm)
- CO2 Measurement: NDIR (Non-Dispersive Infrared
- Alarms: 5,000 TWA, 5,000 ppm, 1.5%, and 3% (default)
- Custom Alarms: 1%, 2%, 2.5%, 3.5%, 4%
- Measurement interval: 2 seconds (0.5Hz)
- Operating Temperature: 32-122°F (0-50°C)
- Calibration: Zero with Nitrogen or Factory Calibration
- Connections: Input/ Output/ Strobe - CAT5 8 pin connector
- Sensor Life Expectancy: > 15 years
Electrical
- Power Supply: 110-220 VAC 50/60 Hz to 12 VDC Power Adapter
- Power Input: 4.5-5.25 VDC
- 24VDC hard-wired power option
- Power Consumption: 300mA peak, 30mA average
- Can be connected to a UPS for Battery Backup
- Horn Strobe: 90-120dB 3KHz, 110 cD
- Max distance any sensor or horn/strobe can be from the tablet is 250 ft.
Warranty
- 1 year - See CO2Meter Terms and Conditions.
Documents
Hoja de Datos en Español (pdf)
Dati Tecnici in Italiano (pdf)
Hard Wiring CM-7000 to CM-1026-5 (pdf)
Hard Wiring CM-7000 to CM-1026-6 (pdf)
CM-7000 Safety Warning Signs (pdf)
Solenoid Valve SV-1027 DataSheet (pdf)
CM-7000 Interactive Landing Page (web)
CM-7000 Video Playlist - Install, Configure, Relays (web)
Accessories
CM-7002 - Reset Unit Add On - the reset unit add-on provides a unique push-button and key switch to mute and reset latch for all sensors connected to the tablet. Click here, to order.
CM-7005 Main Tablet Only - 8" inch touch screen control panel. Contact us, to order.
CM-7006 - Mini Display Tablet - designed for remote display only. Contact us, to order.
CO2 Storage Safety Strobe Tower- designed to provide a flashing indicator, and audible alarm with any of our CM-7000 systems. Click Here, for More.
SV-1027 Solenoid Safety Shut Off Valve - designed to be utilized with our CM-7000 CO2 Multi-Sensor System, and can be directly wired to the SV-1027 24/DC safety shut-off valve via main tablet or sensor unit relays. Click Here, for More.
-
Data Sheets
-
Manuals
-
Technical Documents
-
Videos
-